Power Factor Calculator
Calculate the power factor of a load from real power and apparent power — or from volts, amps and the phase angle between them.
PF = P ÷ S⚡ PF = P ÷ S, or PF = cos θ. The calculator also returns the phase angle, reactive power and the equivalent efficiency of the load.
Power Factor Formulas
From Real & Apparent Power
PF = P(W) ÷ S(VA)The everyday method. You need the real power in watts and the apparent power in volt-amperes.
From Phase Angle
PF = cos θUse the angle between the voltage and current waveforms, measured with a power analyser or phase meter.
Reactive Power
Q = S × sin θThe reactive component of apparent power, measured in volt-amperes reactive (VAR).
The Power Triangle
P² + Q² = S²Real power and reactive power form the two legs of a right triangle; apparent power is the hypotenuse.
How to Calculate Power Factor
Power factor compares the power a circuit actually delivers against the power it has to carry. Because apparent power (VA) = real power (W) ÷ power factor, a load with a PF of 0.8 needs 25% more current capacity than its wattage suggests.
- Measure the real power in watts. This is the useful output of the load — the heat, light or mechanical work it produces.
- Measure the apparent power in volt-amperes. Multiply volts by amps, or read it straight off a power meter or plug-in monitor.
- Divide one by the other. 1,500 W ÷ 1,875 VA = 0.80. The result is a decimal between 0 and 1 — never above 1, since real power can never exceed apparent power.
- Convert to a phase angle if you need one. PF = 0.80 corresponds to a phase angle of about 36.87°.
A good sanity check: if your calculated PF comes out above 1.0, one of the two measurements is wrong. Also confirm that both values were taken under the same load conditions — apparent power rises with current, so a single-phase reading taken while other loads were running will overstate the result.
Power Factor Reference Table
Typical power factors for common loads. Values above 0.95 are generally regarded as good; most industrial tariffs set a threshold of 0.90 or 0.95.
| Load Type | Typical PF | Phase Angle | Current for 10 kW at 400V |
|---|---|---|---|
| Resistive (heaters, incandescent) | 1.00 | 0.0° | 14.4 A |
| Motor — full load, large | 0.85 | 31.8° | 17.0 A |
| Motor — full load, small | 0.75 | 41.4° | 19.2 A |
| Motor — part load | 0.50 | 60.0° | 28.9 A |
| Fluorescent lighting (with ballast) | 0.85 | 31.8° | 17.0 A |
| LED lighting (with driver) | 0.90 | 25.8° | 16.0 A |
| Switch-mode power supply | 0.95 | 18.2° | 15.2 A |
| Welding equipment | 0.55 | 56.6° | 26.2 A |
| Transformers (magnetising) | 0.30 | 72.5° | 48.1 A |
How Many Amps...? (Power Factor in Action)
10 kW at 400V three-phase
At PF 1.0 the current is 14.4 A. At PF 0.8 it rises to 18.0 A — the same 10 kW of useful power, more current on the cable.
Correcting a motor
A 30 kW motor at PF 0.75 draws 57.7 A at 400V. Adding correctly sized capacitors can lift PF to 0.95 and bring that down to 45.6 A.
Working out capacitor size
Reactive power Q = P × tan(arccos PF). Correcting 30 kW from 0.75 to 0.95 needs about 16.6 kVAR of capacitance.
Why PF matters on your bill
Most industrial tariffs charge a penalty below their threshold — often 0.90 or 0.95 — and the penalty rises the further below it you fall.
PF of a home socket
Modern switch-mode supplies push PF above 0.95. Older chargers and halogen transformers often sit around 0.6–0.7.
Leading versus lagging
Inductive loads lag (current after voltage) and capacitive loads lead. Capacitor correction is only needed for lagging loads — over-correcting makes the PF leading, which some tariffs penalise too.
Frequently Asked Questions
How to calculate power factor?
Divide the real power (in watts) by the apparent power (in volt-amperes): PF = P ÷ S. A 1,500 W load drawing 1,875 VA has a power factor of 0.80. Alternatively, PF = cos θ, where θ is the phase angle between the voltage and current waveforms.
What is a good power factor?
0.95 or better is generally considered good, and most utilities require at least 0.90 to avoid penalties. A perfect power factor of 1.0 means real power equals apparent power and all current is doing useful work.
Why is a low power factor penalised?
A low power factor means more current flows for the same useful power. That current heats the supply cables, causes greater voltage drop and increases losses in the distribution network, so utilities pass that cost on to the customer.
What causes a poor power factor?
Inductive loads — motors, transformers, fluorescent ballasts, welding machines and older switch-mode power supplies — draw current that lags behind the voltage. Capacitive loads such as capacitor banks cause the opposite problem, where current leads the voltage.
How do you correct power factor?
Install capacitors in parallel with the inductive load. The leading current from the capacitors offsets the lagging current from the motors, raising the overall power factor without changing the useful power delivered.
What is the difference between real power, apparent power and reactive power?
Real power (W) does useful work. Apparent power (VA) is the total power the circuit must carry. Reactive power (VAR) is the wasted portion stored in magnetic or electric fields. The power triangle relates them: P² + Q² = S².
⚠️ Safety & Electrical Disclaimer
This calculator provides theoretical power factor calculations based on standard AC power relationships. It does NOT determine circuit breaker requirements, conductor wire gauge sizes, capacitor sizing for correction equipment, or compliance with local electrical codes (such as NEC or IEC). Power factor penalties and thresholds vary by utility, tariff and jurisdiction — always confirm the applicable rate with your electricity provider. Capacitor installation involves stored charge and must be carried out by a qualified engineer. Always consult a licensed electrician and your local authority having jurisdiction (AHJ) for physical wiring projects.
Related Electrical Calculators
Related Electrical Tools & Testing Gear
Disclosure: We may earn a commission from purchases made through these links.
Power Quality Analysers
Log real power, apparent power and phase angle over a full production cycle.
ProfessionalPlug-in Power Monitors
Read watts, VA and PF straight from a wall socket for a quick audit.
PopularClamp Meters with PF
Measure current and power factor on a live circuit without disconnecting it.
Top Essential